A hoist motor tripped on a damp morning and you have a megohmmeter in hand. The number only means something if the test is done the same way every time. Motors that reach our dock with surprise insulation failures rarely come with readings anyone wrote down.
Electrical Motor Repair Co. (EMR) is a Trenton, New Jersey shop that tests, repairs and rewinds AC and DC elevator motors for elevator contractors nationwide. Here is how to megger test a hoist motor. Questions about a reading? Call (609) 392 6149.
What does a megger test tell you about a hoist motor?
A megger test applies a DC voltage between a winding and the motor frame and measures how much resistance the insulation offers. High, stable readings mean clean, dry insulation. Low or falling readings point to moisture, conductive carbon dust, oil contamination or insulation that is breaking down with age and heat.
How do you megger test an elevator hoist motor, step by step?
Skip the first three steps and good motors get condemned while bad ones go back in service.
- Lock out. Open, lock and tag the mainline disconnect and verify zero voltage at the motor leads.
- Disconnect the motor. Lift the motor leads at the controller or drive. Test voltage can damage drive electronics and spoil the reading.
- Clean and inspect. Blow out conductive carbon dust from the brush rigging and commutator area and check for oil and moisture, common causes of low readings.
- Set the test voltage. Match it to the motor rating. IEEE 43 calls for 500 volts DC on windings rated below 1,000 volts, which covers most hoist motors.
- Test each circuit. On a DC motor, test the armature, shunt field, series field and interpoles, and brake coil separately to the frame, with the other circuits grounded. On an AC motor, test the stator to ground.
- Read at one minute. Record the one minute reading with winding temperature and humidity, and correct readings to 40 degrees Celsius before comparing them.
- Check the polarization index. Divide the ten minute reading by the one minute reading. For Class B, F and H insulation, 2.0 or more indicates dry, clean windings, and a ratio near 1.0 suggests moisture or contamination.
- Discharge the winding. Ground the winding for several times as long as the test ran before touching the leads. A large winding can hold a dangerous charge.
- Compare readings. Log results by circuit, date and temperature. A steady decline across several tests tells you more than any single number.
What is a good megger reading for an elevator motor?
There is no single number. The IEEE 43 recommended practice sets minimums corrected to 40 degrees Celsius: 100 megohms for most DC armatures and form wound windings built after about 1970, 5 megohms for most random wound windings rated below 1,000 volts, and rated kilovolts plus 1 megohm for field windings and older insulation.
Healthy hoist motors read far above those floors, so a falling trend is the real warning.
What should you do when a hoist motor reads low?
Do not run it until you know why. Clean out the carbon dust, dry the windings, and test again. If the reading recovers, the motor needs cleaning and revarnishing. If it stays low, the insulation itself has failed, and the armature or field coils need reinsulation or a rewind.
Our elevator motor cleaning and maintenance service handles the first case and our elevator motor repair services handle rewinds. For Otis 219HT armatures, see our Armature Reinsulation and Maintenance (ARM) program, and our post on why elevator motors fail explains where the dust comes from.
For a second opinion, call (609) 392 6149 with the nameplate and your readings. On DC gearless machines, our motor testing and diagnostics program adds a field coil drop test and a bar to bar commutator test to the megohmmeter checks.
For shop practice during repair and rewinding, see ANSI/EASA AR100.
Frequently Asked Questions
A megger test is an insulation resistance test made with a megohmmeter, which applies a high DC voltage and reads resistance in megohms. On a hoist motor it shows how well the insulation separates each winding from the frame.
Not a healthy motor at the right test voltage. The risk is to drive electronics left connected and to insulation that is already badly weakened. If in doubt, call (609) 392 6149.
A yearly reading at the same point in the maintenance cycle is a sensible minimum, plus a test whenever a motor trips, gets wet or sits idle. If a reading has dropped, call (609) 392 6149.
A megger test checks insulation from the winding to ground. A surge comparison test sends fast voltage pulses through a winding to find weak insulation between turns, which a megger cannot see.